Description
Marine fixed dry chemical powder system is an important fire suppression system and designed specially for LPG and LNG. It mainly include dry chemical powder skid unit, dry chemical powder monitor, hose station, pneumatic control cabinet and dry chemical powder applicator.
Approval Standard:
1. Chapter 11 of Rules for Construction and Equipment of Ships Carrying Liquefied Gases in Bulk 2018, China Classification Society
2. The Chapter 11 of International Code for The Construction and Equipment of Ships Carrying Liquefied Gases in Bulk and Its Amendments
3. Guildines for the Approval of Fixed Dry Chemical Pwoder Fire-extinguishing Systems for the Protection of Ships Carrying Liquefied Gases in Bulk
4. GB 16668-2010 <General technical specifications for powder extinguishing system and components>
Specification:
Model: | ZFPC | ||
Dry Chemical Powder Tank Volume (L) | 500/750/1000/1500/2000/2500/3000/4000/
5000/6000/7000/8000/9000/10000 |
||
System Working Pressure (MPa) | 1.0~1.6 | ||
Driven Gas | N2 | ||
Pressure of N2 Bottle (MPa) | 14.7 | ||
Volume of N2 Bottle (L) | 4/40/50/68 | ||
Spray Equipment | Dry Chemical Powder Monitor | Dry Chemical Powder Applicator | |
Model | FPC-10/15/25/35/40/45/50 | FQ3.5 | FQ5 |
Discharge Rate (kg/s) | 10/15/25/35/40/45/50 | 3.5 | 5 |
Throw Range (m) | 18/20/30/38/40/45/50 | ≥12 |